| Municipal |
Vendor: CenterPoint
Pull: 6000 Amps @ 480 Volt 3-Phase over 2 Transformers
Service level: Critical Customer -
similar to Hospital Service level
|
Vendor: CenterPoint
Pull: 6000 Amps @ 480 Volt 3-Phase over 2 Transformers
Service level: Critical Customer -
similar to Hospital Service level |
| Generators |
Generator 1
Power Plant: 16 Cylinder 3000 horse
power Cummins Marine
Grade Diesel Gen Set:ONAN
Wattage: 1250 Kw
Deployment: Load Sharing
Generator 2
Power Plant: 16 Cylinder 3000 horse power Cummins Marine
Grade Diesel Gen Set: ONAN
Wattage: 1500 Kw
Deployment: Load Sharing
Generator 3
Power Plant: 16 Cylinder 3000 horse power Cummins Marine
Grade Diesel Gen Set: ONAN
Wattage: 2000 Kw
Deployment: Load Sharing
All three Generators share the load at DC1 with the help of paralleling gear. When a service outage occurs all three generators will start for 10 minutes. If the total load is less then 60% of capacity of one generator, then the other generators will shutdown automatically. If the load reaches 80% of capacity of one generator the other generators will restart
The Power plants are tested weekly.
The Generators are load tested monthly.
The system is inspected quarterly.
|
Generator 1
Power Plant: 16 Cylinder 3000 horse
power Cummins Marine
Grade Diesel Gen Set:ONAN
Wattage: 2000 Kw
Deployment: Load Sharing
Generator 2
Power Plant: 16 Cylinder 3000 horse power Cummins Marine
Grade Diesel Gen Set: ONAN
Wattage: 2000 Kw
Deployment: Load Sharing
Generator 3
Power Plant: 16 Cylinder 3000 horse power Cummins Marine
Grade Diesel Gen Set: ONAN
Wattage: 2000 Kw
Deployment: Load Sharing
All three Generators share the load at DC2 with the help of paralleling gear. When a service outage occurs all three generators will start for 10 minutes. If the total load is less then 60% of capacity of one generator, then the other generators will shutdown automatically. If the load reaches 80% of capacity of one generator the other generators will restart
The Power plants are tested weekly.
The Generators are load tested monthly.
The system is inspected quarterly.
|
| Power Switching |
In the event of a service outage from CenterPoint, the generators will turn over and power will be switched automatically in seconds. This system is tested every month. |
In the event of a service outage from CenterPoint, the generators will turn over and power will be switched automatically in seconds. This system is tested every month. |
| UPS |
Currently there are 5 375 Kw Mitsubishi |
Currently there are 4-375 and 4-500 KVA Mitsubishi |
| Cooling |
AC Units: Data Aire 30 Ton
Number of Units: 30
Total tonnage: 900 Tons
|
AC Units: Liebert 30 Ton
Number of Units: 34
Total tonnage: 1020 Tons
|
|
|
|
|
 |
Redundant power to the network
All 10 backbone routers and top-level network equipment are fed from multiple power feeds, reducing the exposure to power equipment failure.
Redundant fiber connections
Every gigabit Ethernet connection (and DC2 has 13) arrives from two sources and enters the facility at different points
Redundant network cores in both data centers
A fully redundant network means that if a router or high-level network appliance goes down, there is no loss of service.
Individual router per gigabit link
If any router fails, it can only affect one network link, eliminating a major point of failure other competitors allow.
Gigabit cross-connects between both data centers
Data moves quickly between data centers. And if one data center were to experience network connectivity issues, it could simply route data out through the other.
RouteScience at both data centers
Our systems can measure the latency of certain network routes and send client data along the best possible route out to the Internet.
Advanced virus, worm and anti-DoS protection on all network cores
Our goal is to stop attacks before they occur while keeping the safe traffic flowing at top speed.
|
| |
Fireslayer (™) Anti Denial of Service (DOS) Protection |
| |
TippingPoint Intrusion Prevention System (IPS) |
| |
Remote KVM |
| |
Remote Serial Console |
| |
Remote O/S Install |
|
|
|
|
 |
|